Description
Technical
-
- Standards:
- IEC/EN 60898-1
-
- Tripping Characteristic:
- C
-
- Rated Operational Voltage:
- acc. to IEC 60898-1 230 / 400 V AC
-
- Operational Voltage:
- Maximum (Incl. Tolerance) 253 V AC
Minimum 12 V AC
-
- Rated Insulation Voltage (Ui):
- acc. to IEC/EN 60664-1 440 V
-
- Rated Impulse Withstand Voltage (Uimp):
- 4 kV
at 2000 m 5 kV
at Sea Level 6.2 kV
-
- Dielectric Test Voltage:
- 50/60 Hz, 1 min: 2 kV
-
- Input Voltage Type:
- AC
-
- Rated Current (In):
- 25 A
-
- Rated Short-Circuit Capacity:
- (AC) 10 kA
(230 / 400 V AC) 10 kA
-
- Rated Conditional Short-Circuit Current (Inc):
- (230 V) 25 kA
(400 V) 25 kA
-
- Rated Frequency (f):
- 50 / 60 Hz
-
- Power Loss:
- 3.2 W
at Rated Operating Conditions per Pole 3.2 W
-
- Power Supply Connection:
- Arbitrary
-
- Contact Position Indication:
- ON / OFF
-
- Energy Limiting Class:
- 3
-
- Electrical Endurance:
- 20000 AC cycle
-
- Mechanical Endurance:
- 20000 cycle
-
- Number of Poles:
- 1
-
- Number of Protected Poles:
- 1
-
- Overvoltage Category:
- III
-
- Tightening Torque:
- 2 N·m
-
- Actuator Type:
- Toggle
-
- Screw Terminal Type:
- Cage Terminal
-
- Actuator Marking:
- I / O
-
- Actuator Material:
- Insulation Group II, Black, Sealable
-
- Housing Material:
- Insulation Group II, RAL 7035
-
- Mounting on DIN Rail:
- TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
-
- Mounting Position:
- Any
-
- Recommended Screw Driver:
- Pozidriv 2
-
- Accessories Available:
- Yes
-
- Connecting Capacity:
- Conductor 25 / 25 mm²
Flexible with Ferrule 0.75 … 16 mm²
Flexible 0.75 … 16 mm²
Rigid 0.75 … 25 mm²
Stranded 0.75 … 25 mm²
-
- Installation Size:
- acc. to DIN 43880 1
-
- Terminal Type:
- Screw Terminals