Description
Technical Specifications
| Accuracy (from applied pressure): (model 2500) | Pressure < 125 Pa = 1 % + ±2 Pa Pressure > 125 Pa = 1 % + ±1 Pa | 
| Accuracy (from applied pressure): (model 7000) | Pressure < 125 Pa = 1.5 % + ±2 Pa Pressure > 125 Pa = 1.5 % + ±1 Pa | 
| Measuring units: | Pressure: Pa, kPa, mbar, inchWC, mmWC, psi Flow: m3/s, m3/hr, cfm, l/s, m/s, ft/min | 
| Control signal: | 0…10 V or 4…20 mA (selectable by jumper) | 
| Output signal for pressure or air flow (selectable via menu): | 0…10 VDC, Load R minimum 1 kΩ or 4…20 mA, maximum load 500 Ω (selectable by jumper) | 
| PID-parameters: | Adjustable via menu | 
| Zero point calibration: | Automatic with autozero element (-AZ) or by pushbutton | 
| Supply voltage: | 24 VDC ±10 % / 24 VAC ±10 % | 
| Power consumption: | < 1.0 W | 
| Operating temperature: | -10…+50 °C (with autozero calibration -5…+50 °C) | 
| Protection standard: | IP54 | 


 
	 
	
 
	 
	 
	 
	 
	 
	